SANS 1713 Medium Voltage ABC cable range: 3.8/6.6kV, 6.35/11kV, 12.7/22kV , 19/33kV
MV ABC Wire Application
Suitable for aerial installation and for public power distribution networks
MV ABC Wire Standard
SANS 1713— Electric cables -Medium voltage aerial bundled conductors for voltages from 3,8/6,6 kV to 19/33 kV
MV ABC Wire Construction

Size Range -Type A (Armoured) 95- 185 mm²(3.8/6,6kV, 6.35/11kV, 12.7/22kV,19/33kV)
Size Range -Type B (Unarmoure) 35 – 185 mm²(3.8/6,6kV, 6.35/11kV, 12.7/22kV)50- 185 mm2(19/33kV)
- 1.Conductor: Aluminum, circular stranded and compacted.
- 2.Conductor Screening: Extruded thermosetting semi-conductor layer.
- 3.Insulation: XLPE thermosetting material.
- 4.Insulation Screening: Semi conducting screen: Extruded thermosetting semi-conducting layer, applied under a swellable semi-conducting tape for water tightness.
- 5.Metal screen: Plain soft copper wire and / or copper tape applied helically, or aluminum tape applied longitudinally bonded to the outer PE sheath.
- 6.Outer sheath: Extruded black PE sheath, or PVC upon specific customer requirements.
- 7.Steel Messenger: 50 or 70 mm² galvanized steel stranded wires, covered with black PE, or PVC upon specific customer requirements.
3,8/6,6 kV to 19/33 kV Medium Voltage Aerial Bundled Conductors Specifications
| 6.6kV ABC Cable Specification | ||||||||
| Phase Core | ||||||||
| Conductor size | mm2 nom | 35 | 50 | 70 | 95 | 120 | 150 | 185 |
| Conductor diameter | mm app. | 7.15 | 8.25 | 9.95 | 11.8 | 13.1 | 14.8 | 15.95 |
| Insulation diameter | mm app. | 15.4 | 16.5 | 18.2 | 20.1 | 21.4 | 22.7 | 24.2 |
| Core sheath diameter | mm app. | 20.5 | 21.6 | 23.5 | 25.5 | 26.8 | 28.1 | 29.9 |
| Catenary (Support Core) | ||||||||
| Conductor size | mm2 nom | 50 | 50 | 50 | 50 | 70 | 70 | 70 |
| Conductor diameter | mm app. | 9 | 9 | 9 | 9 | 10.8 | 10.8 | 10.8 |
| Insulation diameter | mm app. | 11.5 | 11.5 | 11.5 | 11.5 | 13.3 | 13.3 | 13.3 |
| Maximum tensile strength and pulling force of catenary | kN | 26 | 26 | 26 | 26 | 37 | 37 | 37 |
| Cable | ||||||||
| Cable diameter | mm app. | 44 | 47 | 51 | 55 | 58 | 61 | 65 |
| Cable mass | kg/m app. | 2.05 | 2.24 | 2.6 | 3.01 | 3.51 | 3.85 | 4.33 |
| Gross mass (500m) | kg app. | 915 | 973 | 1,079 | 1,204 | 1,354 | 1,454 | 1,599 |
| Bending radius | mm min. | 636 | 669 | 720 | 776 | 841 | 880 | 926 |
| Current rating | ||||||||
| In air | Amps | 150 | 185 | 230 | 280 | 325 | 370 | 430 |
| Resistance | ||||||||
| dc @ 20°C | W/km max | 0.868 | 0.641 | 0.443 | 0.32 | 0.253 | 0.206 | 0.164 |
| ac @ 90°C | W /km max | 1.113 | 0.822 | 0.568 | 0.411 | 0.325 | 0.265 | 0.211 |
| Reactance | W /km | 0.136 | 0.124 | 0.121 | 0.114 | 0.111 | 0.106 | 0.103 |
| Impedance | W /km | 1.121 | 0.832 | 0.581 | 0.426 | 0.342 | 0.284 | 0.233 |
| Short circuit ratings | ||||||||
| Symmetrical | kA (1 sec) | 3 | 4 | 5.8 | 8 | 10.2 | 12.5 | 15.7 |
| Earth fault | kA (1 sec) | 1.5 | 1.6 | 1.7 | 1.9 | 2 | 2.1 | 2.3 |
| 11kv ABC Cable Specification | ||||||||
| Phase Core | ||||||||
| Conductor size | mm2 nom | 35 | 50 | 70 | 95 | 120 | 150 | 185 |
| Conductor diameter | mm app. | 7.15 | 8.25 | 9.95 | 11.8 | 13.1 | 14.8 | 16.35 |
| Insulation diameter | mm app. | 17.3 | 18.4 | 20.1 | 21.9 | 23.2 | 24.5 | 26.1 |
| Core sheath diameter | mm app. | 22.5 | 23.6 | 25.3 | 27.4 | 28.7 | 30.2 | 31.7 |
| Catenary (Support Core) | ||||||||
| Conductor size | mm2 nom | 50 | 50 | 50 | 50 | 70 | 70 | 70 |
| Conductor diameter | mm app. | 9 | 9 | 9 | 9 | 10.8 | 10.8 | 10.8 |
| Insulation diameter | mm app. | 11.5 | 11.5 | 11.5 | 11.5 | 13.3 | 13.3 | 13.3 |
| Maximum tensile strength and pulling force of catenary | kN | 26 | 26 | 26 | 26 | 37 | 37 | 37 |
| Cable | ||||||||
| Cable diameter | mm app. | 49 | 51 | 55 | 59 | 62 | 65 | 69 |
| Cable mass | kg/m app. | 2.31 | 2.52 | 2.85 | 3.28 | 3.61 | 3.99 | 4.43 |
| Gross mass (500m) | kg app. | 993 | 1,055 | 1,155 | 1,285 | 1,382 | 1,496 | 1,628 |
| Bending radius | mm min. | 691 | 724 | 775 | 831 | 896 | 935 | 981 |
| Current rating | ||||||||
| In air | Amps | 150 | 185 | 230 | 280 | 325 | 370 | 430 |
| Resistance | ||||||||
| dc @ 20°C | W/km max | 0.868 | 0.641 | 0.443 | 0.32 | 0.253 | 0.206 | 0.164 |
| ac @ 90°C | W /km max | 1.113 | 0.822 | 0.568 | 0.411 | 0.325 | 0.265 | 0.211 |
| Reactance | W /km | 0.136 | 0.124 | 0.121 | 0.114 | 0.111 | 0.106 | 0.103 |
| Impedance | W /km | 1.121 | 0.832 | 0.581 | 0.426 | 0.342 | 0.284 | 0.233 |
| Short circuit ratings | ||||||||
| Symmetrical | kA (1 sec) | 3 | 4 | 5.8 | 8 | 10.2 | 12.5 | 15.7 |
| Earth fault | kA (1 sec) | 1.5 | 1.6 | 1.7 | 1.9 | 2 | 2.1 | 2.3 |
| 22kV ABC Cable Specification | ||||||||
| Phase Core | ||||||||
| Conductor size | mm2 nom | 35 | 50 | 70 | 95 | 120 | 150 | 185 |
| Conductor diameter | mm app. | 7.15 | 8.25 | 9.95 | 11.8 | 13.1 | 14.8 | 16.35 |
| Insulation diameter | mm app. | 21.6 | 22.7 | 24.4 | 26.2 | 27.5 | 29.2 | 30.8 |
| Core Sheath diameter | mm app. | 27 | 28.1 | 30 | 31.9 | 33.4 | 35.1 | 36.8 |
| Catenary (Support Core) | ||||||||
| Conductor size | mm2 nom | 50 | 50 | 50 | 50 | 70 | 70 | 70 |
| Conductor diameter | mm app. | 9 | 9 | 9 | 9 | 10.8 | 10.8 | 10.8 |
| Insulation diameter | mm app. | 11.5 | 11.5 | 11.5 | 11.5 | 13.3 | 13.3 | 13.3 |
| Maximum Tensile Strength and Pulling force of Catenary | kN | 26 | 26 | 26 | 26 | 37 | 37 | 37 |
| Cable | ||||||||
| Cable diameter | mm app. | 58 | 61 | 65 | 69 | 72 | 76 | 80 |
| Cable mass | kg/m app. | 2.96 | 3.19 | 3.61 | 4.05 | 4.63 | 5.06 | 5.61 |
| Gross mass (500m) | kg app. | 1 188 | 1 257 | 1 383 | 1 514 | 1 690 | 1 819 | 1 984 |
| Bending radius | mm min. | 821 | 854 | 905 | 960 | 1025 | 1076 | 1123 |
| Current rating | ||||||||
| In air | Amps | 150 | 185 | 230 | 280 | 325 | 370 | 430 |
| Resistance | ||||||||
| dc @ 20°C | W/km max | 0.868 | 0.641 | 0.443 | 0.32 | 0.253 | 0.206 | 0.164 |
| ac @ 90°C | W /km max | 1.113 | 0.822 | 0.568 | 0.411 | 0.325 | 0.265 | 0.211 |
| Reactance | W /km | 0.136 | 0.124 | 0.121 | 0.114 | 0.111 | 0.106 | 0.103 |
| Impedance | W /km | 1.121 | 0.832 | 0.581 | 0.426 | 0.342 | 0.284 | 0.233 |
| Short circuit ratings | ||||||||
| Symmetrical | kA (1sec) | 3 | 4 | 5.8 | 8 | 10.2 | 12.5 | 15.7 |
| Earth fault | kA (1sec) | 1.5 | 1.6 | 1.7 | 1.9 | 2 | 2.1 | 2.3 |
| 33kV ABC Cable Specification | ||||||||
| Phase Core | ||||||||
| Conductor size | mm2 nom | 50 | 70 | 95 | 120 | 150 | 185 | |
| Conductor diameter | mm app. | 8.25 | 9.95 | 11.8 | 13.1 | 14.8 | 16.35 | |
| Insulation diameter | mm app. | 27.8 | 29.5 | 314 | 32.7 | 34 | 35.5 | |
| Core Sheath diameter | mm app. | 33.7 | 35.4 | 37.4 | 38.7 | 40.2 | 41.8 | |
| Catenary (Support Core) | ||||||||
| Conductor size | mm2 nom | 50 | 50 | 50 | 70 | 70 | 70 | |
| Conductor diameter | mm app. | 9 | 9 | 9 | 10.8 | |10.80 | 10.8 | |
| Insulation diameter | mm app. | 11.5 | 11.5 | 11.5 | 13.3 | 13.3 | 13.3 | |
| Maximum Tensile Strength and Pulling force of Catenary | kN | 26 | 26 | 26 | 37 | 37 | 37 | |
| Cable | ||||||||
| Cable diameter | mm app. | 73 | 76 | 81 | 84 | 87 | 90 | |
| Cable mass | kg/m app. | 4.12 | 4.53 | 5.06 | 5.37 | 5.82 | 6.33 | |
| Gross mass (500m) | kg app. | 1,535 | 1,658 | 1,819 | 1,910 | 2,046 | 2,200 | |
| Bending radius | mm min. | 1007 | 1058 | 1114 | 1179 | |1218 | 1264 | |
| Current rating | ||||||||
| In air | Amps | 185 | 230 | 280 | 325 | 370 | 430 | |
| Resistance | ||||||||
| dc @ 20°C | W/km max | 0.641 | 0.443 | 0.32 | 0.253 | 0.206 | 0.164 | |
| ac @ 90°C | W/km max | 0.822 | 0.568 | 0.411 | 0.325 | 0.265 | 0.211 | |
| Reactance | W /km | 0.124 | 0.121 | 0.114 | 0.111 | 0.106 | 0.103 | |
| Impedance | W /km | 0.832 | 0.581 | 0.426 | 0.342 | 0.284 | 0.233 | |
| Short circuit ratings | ||||||||
| Symmetrical | kA (1 sec) | 4 | 5.8 | 8 | 10.2 | 12.5 | 15.7 | |
| Earth fault | kA (1 sec) | 1.6 | 1.7 | 1.9 | 2 | 2.1 | 2.3 | |
Certificate Display
Factory Tour
Why choose us?
Professional
Professional
Fast Delivery
Fast Delivery
Good Price
Good Price
High Quality
High Quality
FAQs
Who are we?
Uni Cable Group is a trusted supplier of overhead line products, power cables and cable manufacturing materials based in China. Backed by experienced manufacturing resources and a professional export team, we serve utilities, EPC contractors, distributors and cable manufacturers worldwide with reliable supply, technical support and OEM solutions.
How can we guarantee quality?
What can you buy from us?
House eletric wire, Anti-aging wire, Solar PV cable, Control cable, Shielded computer cable, Low/Medium/High Voltage power cable, Aluminum alloy cable, Aerial insulated cable, Steel core aluminum standed wire, LSZH cable, Fireproof cable, Wind power cable, EV charging cable, Energy storage cable, Mining cable, etc.
Why should you buy from us not from other suppliers?
We are committed to providing reliable products, competitive pricing and responsive service for customers worldwide. With an integrated manufacturing network, strict quality control and one-stop supply capabilities, we simplify global cable sourcing and create long-term value for our partners.
What services can we provide?
Accepted Delivery Terms: FOB,CFR,EXW,FAS,DDP; Accepted Payment Currency:USD,EUR,CAD,AUD,GBP,CNY; Accepted Payment Type: T/T,L/C,MoneyGram,Credit Card,Western Union,Cash; Language Spoken:English,Chinese,Japanese,German,Russian
If I need customize Packing Cartons, is that available?
Yes, we have production line for packing box and cartons. we can make it according to your special requirement. If you are interested in our goods , please kindly send an inquiry to us !
Contact us to get your quote!
Products
Related Products
Uni Cable Group provides a comprehensive range of overhead conductors, power cables and cable manufacturing materials, supported by experienced manufacturing resources and strict quality control to meet international project requirements.
our products
NEED HELP
Contact Info
- Email: info@unicablegroup.com
- Phone: +86 15649859836
- WeChat: +86 15649859836
- WhatsApp: +86 15649859836
- Address: Shenglong Center, Hanghai Middle Road, Erqi District, Zhengzhou City, Henan Province, China
© Copyright 2025 by Uni Cable Group All Rights Reserved.